Page 34 blueplanet Operating and Installation Instructions 1502x - 2502x
Installation and Start-Up
5.8 Starting up the inverter
After completing the mechanical and electrical installation, the
inverter is put into operation as follows:
NOTE
The inverter can be put into operation only under daylight
conditions (i.e. at a solar generator voltage of > 100 V).
If no daylight or solar generator voltage is present, the
inverter can be activated by pressing the night start key if
there is AC voltage present (see section „Dimensions and
weights“ in the Operating Instructions). However, normal
operation is not possible in this condition. Only the values
can be read off the display.
ACTION
Assure voltage supply
Switch on th external AC/DC disconnect switch
(0 1).
During the initial start-up, the corresponding country and
language must be selected. Select the appropriate language
using the ‘2’ (right) key, press the ‘1’ (left) key to advance to
the country selection. Press the ‘2’ key to advance through the
various grid types. Once the proper grid type is selected press
the ‘1’ key then press both the ‘1’ and ‘2’ keys at the same time
to save the settings. If the improper grid settings were selected,
hold down the ‘2’ key to start the process again.
NOTE
If the power is cycled or 10 minutes elapse the settings for
the grid type are locked and a password will need to be
obtained from tech support.
The top green LED “OK” lights when DC voltage is available
and indicates that it is ready to be put into operation. The
display now indicates the current PV generator voltage “Start
from xx V, meas.: xxx V. If the measured voltage is greater
than the starting voltage, the unit will start grid-feeding after
a country-specifi c waiting time. This start-up waiting period
is required in order to ensure that the generator voltage is
continuously above the power delivery limit of 125 V (1502x)
and 200 V (2502x).
A quick start routine is provided for startup and test purposes.
This routine circumvents the start-up delay period. This quick
start routine is found in the confi guration mode menu (see
Operating Instructions).
During the normal start-up procedure, the line relays audibly
switch on after a country-specifi c waiting time and the feed-
ing of the grid starts. This is indicated by the middle green
LED with the house and power line symbol next to it. The
display now shows the power being fed into the grid. Key ‘1
(left) can now be used to display the various measured values
(see„Dimensions and weights“).
5.9 Parameter programming
Various operating mode parameters can be set in the param-
eter mode menu of blueplanet units.
!
WARNING
Wrong parameter settings can lead to loss of
functionality as well as render your system
unsafe.
Modifi cations may be made only in exceptional
cases and only after having consulted with the
manufacturer and the utility company.
Parameter menu
Country selection
Line under voltage switch-off
Line over voltage switch-off
Under frequency switch-off
Over frequency switch-off
Starting voltage 125 V (1502x) /
200 V (2502x)
Figure 27: Parameter menu
ACTION
To switch to programming mode, hold down key2 for
approx. 20 seconds. Use key “1” to scroll through the various
menu items. The menu is continuous. When you reach the
end, the display automatically returns to the fi rst item.
NOTE
After the country and grid type have been set, and either
the inverter is powered down or 10 minutes have elapsed,
and a change to the country or grid type is needed, a pass
code must be obtained from KACO support. Please have
the inverter serial number available when calling to obtain
the pass code.